Single-function double-timer relay
1 contact 1 time function 8 time ranges
Time measurement circuit data
Cyclic operation with two independent times T1 and T2.
Operation with function Ii or Ip depends on the state of the control contact S.
Ii - Switching on the supply voltage U when the control contact S is open
Ip- Switching on the supply voltage U when the control contact S is closed
- power LED - when the time is not being measured, it lights continuously
- time value and range are read during operation
- triggering - depending on the function being performed
ON - fixed switching on OFF - permanent off
1s,10s, 1min, 10min, 1h, 10h, 1 day, 10 days
Time setting |
fluent - (from 0.1 to 1) x time range (does not apply to the ON/OFF range)
setting accuracy / repeatability
±5% / ±0.5%
Values influencing time settings
green LED U ON - indication of supply voltage U
green LED U flashing slowly - T1 time measurement
green LED U flashing quickly - T2 time measurement
yellow LED R ON/OFF - output relay status
on a 35mm rail according to PN-EN 60715
cross-section 1x2.5mm2 (1x14AWG)
cable stripping length
clamp tightening torque
Output circuit - pin data
number and type of contacts changeoverch
maximum AC contact voltage
AC1 - 16A/250V AC
DC1 - 16A/24V DC
DC1 - 0.3A/250V DC
continuous current-carrying capacity of the contact
maximum switching power in category AC1
minimum switching power
maximum switching frequency
600 cycles/h at rated load in category AC1
Input circuit - pin data
230V 50/60Hz AC terminals A1, A2
12-240V 50/60Hz terminals (+) A1, (-)A2
Operating supply voltage range
AC ≤3.5VA 230V AC 50Hz
AC ≤1.5VA 12-240V AC/DC 50Hz, AC:50Hz
DC 1.5W 12-240V AC/D
power frequency range
Control contact (control terminal S is activated by connecting to terminal A1, via an external control contact S) |
Minimum voltage (at which the control signal is recognizable): 0.7Un
Minimum pulse duration (at which the control signal is recognizable) AC: ≥50ms DC: ≥30ms
Insulation data according to PN-EN 60664-1
rated insulation voltage
rated impulse withstand voltage | 4000V
insulation pollution degree
flammability class according to UL94
housing: V-O
panel front:V-2
Input-output: 4000V AC Insulation type: basic
in the AC1 &
Temperature: ±5%/°C
Supply voltage: ±0.1%/V
AC: ≤150ms 230V AC 50Hz
AC: ≤400ms 12-240V AC/DC AC:50Hz
DC: ≤150ms 12-240V AC/DC
Maximum control line length: 10m
Contact gap: 1000V AC Gap type: incomplete separation