Reduce Downtime - Detect Leakage Current Without Taking Equipment Offline
The Fluke 369 True-rms Leakage Current Clamp Meter records and documents detected leakage current and compares readings between measurements to prevent unplanned downtime and identify intermittent GFCI and RCD tripping. Measurements can be made while the instrument is live.
The Fluke 369's wide 61mm opening makes it ideal for measuring large conductors. The clamp jaws are fully shielded, accurately detecting even the smallest leaks and minimizing external electromagnetic interference.
Key Features
- True RMS provides high accuracy for measuring complex waveforms, even non-sinusoidal ones.
- Opening: 61mm
- Measures up to 60A with a maximum resolution of 1μA.
- Selectable filter function eliminates unwanted noise.
- Measures maximum, minimum, and average values with a hold function.
- LED work light on the front of the instrument allows use in dark wiring cabinets.
- Backlit display. Backlight and auto-off functions extend battery life.
・CAT III 600V safety rating
・Reduced downtime - Detect leaks without taking equipment offline.
□Electrical Specifications□
[Measurement Function] AC
[AC Ampere Range] 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A
[Range Selection] mA / A: Manual Selection
______ 3 mA / 30 mA / 300 mA: Automatic Selection
______ 3 A / 30 A / 60 A: Automatic Selection
[Range/Resolution] 3 mA*1 / 0.001 mA
_______ 30 mA / 0.01 mA
_______ 300 mA / 0.1 mA
________ 3 A / 0.001 A
_______ 30 A / 0.01 A
______60 A / 0.1 A
[Accuracy - Filter Enabled (40 to 70 Hz), Filter Disabled (40 to 1 kHz) *2]
____3 mA to 30 A: 1% + 5 counts
____60 A: 2% + 5 counts
[Frequency] 40 Hz to 1 kHz
[Crest Factor] = "3"
Accuracy is valid for one year after calibration. Accuracy is expressed as ± (% of reading + counts). Reference conditions are 23 ± 5°C (73°F ± 5°F) and maximum relative humidity of 80%.
*1. Minimum value is 10 μA rms.
*2. TC/°C out of range: 18-28°C, 0.02 + 1
□ Physical Specifications □
[Display (LCD)] Digital reading: 3300 counts
[Screen Refresh Rate] 4 times/second
[Maximum Conductor Diameter] 61 mm
[Dimensions] 257 x 116 x 46 mm
[Weight] 600 g
[Batteries] 2 x AA, IEC LR6, NEDA 15A, Alkaline
[Battery Life] Battery life is over 150 hours (without backlight or spotlight).
[Automatic Shutdown] The meter automatically shuts down after 15 minutes of inactivity.
□ Safety and Environmental Specifications □
[General Safety Specifications] IEC 61010-1: Pollution Degree 2
[Measurement Safety] IEC 61010-2-032: CAT III 600 V/CAT IV 300 V
[Operating Temperature] -10°C to +50°C
Storage Temperature: -40°C to +60°C
Operating Humidity: Non-condensing (<10°C)
90% Relative Humidity (10-30°C)
75% Relative Humidity (30-40°C)
45% Relative Humidity (40-50°C)
Protection Class: IEC 60529: IP30 (Jaws Closed)
Operating Altitude: 2000m
Storage Altitude: 12000m
Current Sensor Operating Category: IEC 61557-13: Class 2, ≤ 30A/m
Prevent unplanned downtime and identify intermittent GFCI and RCD tripping by recording and documenting detected leakage currents and comparing readings between measurements. The device can be used to measure live wires.
The 61mm wide opening makes it ideal for measuring large conductors. The clamp jaws are fully shielded, ensuring high accuracy in detecting even the smallest leaks and minimizing external electromagnetic interference.